New
Gamesa Electric PV
3X series - PV Stations

High-power
PV Inverter family

Maximum power
with large flexibility
for best LCoE

Gamesa Electric PV 3X series PV Stations

Gamesa Electric
PV 3X series
PV Stations

Plug & Play MV Solutions

AEP (Advanced Energy Production)
& UEP (Ultra Energy Production)
configurations

better

Better LCoE

Compact design that achieves a high power density obtaining overall cost reduction by using less PV station units per project.

Design with best-in-class components that guarantees less probability of failure and therefore less operation cost (materials and workforce).

Market leading inverter efficiency of 99.5%.

reduction

CAPEX reduction

Less units needed per project, which results in lower equipment cost.

Reduced costs of transportation, offloading and site preparation.

Solution delivered preassembled, configured and tested, reducing on-site labour cost.

puzzle

Flexibility

Wide range of configurations with outputs from 3800 to 9400 kVA and IEC & UL certifications.

Bidirectional inverter that allows PV Station to be configured as part of a Battery Energy Storage System (BESS) in DC and AC coupling topologies.

Customization at PV station subsystems, such as MV transformer, auxiliaries’ system and DC input configuration, according to customer necessities.

link

Plug & play

Fully assembled and tested MV solution.

Quick installation on field, reducing installation time and costs.

Easy to support and mantain.

2 inverters

IEC version
2 Inverters

1 inverters

IEC version
1 Inverter

UL version

UL version
1 Inverter

AEP & UEP configurations

Available to fit any customers' needs

The Gamesa Electric PV 3X series
PV Stations combine maximum power
with large flexibility for best LCoE

PVS 3800 AEP PVS 4000 AEP PVS 4200 AEP PVS 4400 AEP
Number of Inverters 1 x PV 3800 AEP 1 x PV 4000 AEP 1 x PV 4200 AEP 1 x PV 4400 AEP
DC Input
Ratio DC/AC Up to 200%
Max. DC Current @25ºC [77ºF] 2 x 2362 A
Max. DC Current @40ºC [104ºF] 2 x 2100 A
Max. DC Current @55ºC [131ºF] 2 x 2100 A
Max. DC Current @60ºC [140ºF] 2 x 1050 A
DC Voltage Range 835 - 1500 V 875 - 1500 V 915 - 1500 V 955 - 1500 V
DC Voltage Range MPPT 835 - 1300 V 875 - 1300 V 915 - 1300 V 955 - 1300 V
Nr of DC Ports Max 24 fuse +/- monitored
Max 36 fuse + monitored
MPPT 1
AC Output
Nominal AC Power @25ºC [77ºF] 3837 kVA 4029 kVA 4221 kVA 4412 kVA
Nominal AC Power @50ºC [122ºF] 3409 kVA 3579 kVA 3750 kVA 3920 kVA
Nominal AC Power @55ºC [131ºF] 3409 kVA 3579 kVA 3750 kVA 3920 kVA
Nominal AC Power @60ºC [140ºF] 1704 kVA 1789 kVA 1875 kVA 1959 kVA
Nominal AC Voltage 13.8 - 34.5 kV rms
AC Power Frequency 50 / 60 Hz
Reactive Power Range Any
Protective Devices
DC Input Fuse and motorized load disconnector
AC Input Circuit breaker
Overvoltage Protections DC Type 1 + 2 SPD
Components PV Station
Inverter 1 x PV 3800 AEP 1 x PV 4000 AEP 1 x PV 4200 AEP 1 x PV 4400 AEP
Transformer* Dyn KNAN/ONAN
Switchgear* 0L1V / 1L1V / 2L1V up to 36 kV
Custom Auxiliary Transformer Optional
Others Auxilliary cabinet
Communications
Control Modbus TCP / IP (Profinet, CAN upon request)
Monitoring Modbus TCP / IP
Other Features
LVRT Yes
HVRT Yes
Working Ambient Temperature ** -20°C / +60°C (-4ºF / +140ºF). Option -40ºC (-40ºF)
Relative Humidity 100% (without condensation)
Max. Altitude (whithout derating) *** 2000 m (6561ft)
Dimensions W x H x D (IEC / UL version) (1) 11800 x 2600 x 2100 mm / 30 x 8,5 x 8,6 ft
Weight (IEC / UL version) (1) 19000 Kg / 35000 lbs
Protection IP54, NEMA3R
Cooling Liquid & forced air
Main Standards Optionals
IEC 62109 -40°C Low Temperature Kit
UL 1741-SA UPS for Supplying Trackers
UL 62109 Motorized MV Switchgear
NEC High Corrosion Protection Kit
Seismic Reinforcement

(1) UL variant only available for 1-inverter based configuration
* UL version: Padmounted Dyn (without external switchgear)
** With derating from 25ºC / 77ºF
*** Up to 4000 m (13123 ft) with derating, as optional

PVS 7600 AEP PVS 8000 AEP PVS 8400 AEP PVS 8800 AEP
Number of Inverters 2 x PV 3800 AEP 2 x PV 4000 AEP 2 x PV 4200 AEP 2 x PV 4400 AEP
DC Input
Ratio DC/AC Up to 200%
Max. DC Current @25ºC [77ºF] 4 x 2362 A
Max. DC Current @40ºC [104ºF] 4 x 2100 A
Max. DC Current @55ºC [131ºF] 4 x 2100 A
Max. DC Current @60ºC [140ºF] 4 x 1050 A
DC Voltage Range 835 - 1500 V 875 - 1500 V 915 - 1500 V 955 - 1500 V
DC Voltage Range MPPT 835 - 1300 V 875 - 1300 V 915 - 1300 V 955 - 1300 V
Nr of DC Ports Max 24 fuse +/- monitored
Max 36 fuse + monitored
MPPT 1
AC Output
Nominal AC Power @25ºC [77ºF] 7674 kVA 8058 kVA 8442 kVA 8824 kVA
Nominal AC Power @50ºC [122ºF] 6818 kVA 7158 kVA 7500 kVA 7840 kVA
Nominal AC Power @55ºC [131ºF] 6818 kVA 7158 kVA 7500 kVA 7840 kVA
Nominal AC Power @60ºC [140ºF] 3409 kVA 3579 kVA 3750 kVA 3920 kVA
Nominal AC Voltage 13.8 - 34.5 kV rms
AC Power Frequency 50 / 60 Hz
Reactive Power Range Any
Protective Devices
DC Input Fuse and motorized load disconnector
AC Input Circuit breaker
Overvoltage Protections DC Type 1 + 2 SPD
Components PV Station
Inverter 2 x PV 3800 AEP 2 x PV 4000 AEP 2 x PV 4200 AEP 2 x PV 4400 AEP
Transformer* Dyn KNAN/ONAN
Switchgear* 0L1V / 1L1V / 2L1V up to 36 kV
Custom Auxiliary Transformer Optional
Others Auxilliary cabinet
Communications
Control Modbus TCP / IP (Profinet, CAN upon request)
Monitoring Modbus TCP / IP
Other Features
LVRT Yes
HVRT Yes
Working Ambient Temperature ** -20°C / +60°C (-4ºF / +140ºF). Option -40ºC (-40ºF)
Relative Humidity 100% (without condensation)
Max. Altitude (whithout derating) *** 2000 m (6561ft)
Dimensions W x H x D (IEC / UL version) (1) 11800 x 2600 x 2100 mm
Weight (IEC / UL version) (1) 25.500 kg
Protection IP54
Cooling Liquid & forced air
Main Standards Optionals
IEC 62109 -40°C Low Temperature Kit
UL 1741-SA UPS for Supplying Trackers
UL 62109 Motorized MV Switchgear
NEC High Corrosion Protection Kit
Seismic Reinforcement

(1) UL variant only available for 1-inverter based configuration
* UL version: Padmounted Dyn (without external switchgear)
** With derating from 25ºC / 77ºF
*** Up to 4000 m (13123 ft) with derating, as optional

PVS 4100 UEP PVS 4300 UEP PVS 4300 UEP PVS 4700 UEP
Number of Inverters 1 x PV 4100 UEP 1 x PV 4300 UEP 1 x PV 4300 UEP 1 x PV 4700 UEP
DC Input
Ratio DC/AC Up to 200%
Max. DC Current @25ºC [77ºF] 2 x 2500 A
Max. DC Current @40ºC [104ºF] 2 x 2220 A
Max. DC Current @55ºC [131ºF] 2 x 2220 A
Max. DC Current @60ºC [140ºF] 2 x 1110 A
DC Voltage Range 835 - 1500 V 875 - 1500 V 915 - 1500 V 955 - 1500 V
DC Voltage Range MPPT 835 - 1300 V 875 - 1300 V 915 - 1300 V 955 - 1300 V
Nr of DC Ports Max 24 fuse +/- monitored
Max 36 fuse + monitored
MPPT 1
AC Output
Nominal AC Power @25ºC [77ºF] 4095 kVA 4299 kVA 4504 kVA 4709 kVA
Nominal AC Power @50ºC [122ºF] 3637 kVA 3819 kVA 4001 kVA 4183 kVA
Nominal AC Power @55ºC [131ºF] 3637 kVA 3819 kVA 4001 kVA 4183 kVA
Nominal AC Power @60ºC [140ºF] 1819 kVA 1910 kVA 2001 kVA 2091 kVA
Nominal AC Voltage 13.8 - 34.5 kV rms
AC Power Frequency 50 / 60 Hz
Reactive Power Range Any
Protective Devices
DC Input Fuse and motorized load disconnector
AC Input Circuit breaker
Overvoltage Protections DC Type 1 + 2 SPD
Components PV Station
Inverter 1 x PV 4100 UEP 1 x PV 4300 UEP 1 x PV 4500 UEP 1 x PV 4700 UEP
Transformer* Dyn KNAN/ONAN
Switchgear* 0L1V / 1L1V / 2L1V up to 36 kV
Custom Auxiliary Transformer Optional
Others Auxilliary cabinet
Communications
Control Modbus TCP / IP (Profinet, CAN upon request)
Monitoring Modbus TCP / IP
Other Features
LVRT Yes
HVRT Yes
Working Ambient Temperature ** -20°C / +60°C (-4ºF / +140ºF). Option -40ºC (-40ºF)
Relative Humidity 100% (without condensation)
Max. Altitude (whithout derating) *** 2000 m (6561ft)
Dimensions W x H x D (IEC / UL version) (1) 11800 x 2600 x 2100 mm / 30 x 8.5 x 8.6 ft
Weight (IEC / UL version) (1) 19500 kg / 36000 lbs
Protection IP54, NEMA3R
Cooling Liquid & forced air
Main Standards Optionals
IEC 62109 -40°C Low Temperature Kit
UL 1741-SA UPS for Supplying Trackers
UL 62109 Motorized MV Switchgear
NEC High Corrosion Protection Kit
Seismic Reinforcement

(1) UL variant only available for 1-inverter based configuration
* UL version: Padmounted Dyn (without external switchgear)
** With derating from 25ºC / 77ºF
*** Up to 4000 m (13123 ft) with derating, as optional

PVS 8200 UEP PVS 8600 UEP PVS 9000 UEP PVS 9400 UEP
Number of Inverters 2 x PV 4100 UEP 2 x PV 4300 UEP 2 x PV 4300 UEP 2 x PV 4700 UEP
DC Input
Ratio DC/AC Up to 200%
Max. DC Current @25ºC [77ºF] 4 x 2500 A
Max. DC Current @40ºC [104ºF] 4 x 2220 A
Max. DC Current @55ºC [131ºF] 4 x 2220 A
Max. DC Current @60ºC [140ºF] 4 x 1110 A
DC Voltage Range 835 - 1500 V 875 - 1500 V 915 - 1500 V 955 - 1500 V
DC Voltage Range MPPT 835 - 1300 V 875 - 1300 V 915 - 1300 V 955 - 1300 V
Nr of DC Ports Max 24 fuse +/- monitored
Max 36 fuse + monitored
MPPT 1
AC Output
Nominal AC Power @25ºC [77ºF] 8190 kVA 8598 kVA 9008 kVA 9418 kVA
Nominal AC Power @50ºC [122ºF] 7274 kVA 7638 kVA 8002 kVA 8366 kVA
Nominal AC Power @55ºC [131ºF] 7274 kVA 7638 kVA 8002 kVA 8366 kVA
Nominal AC Power @60ºC [140ºF] 3638 kVA 3820 kVA 4002 kVA 4182 kVA
Nominal AC Voltage 13.8 - 34.5 kV rms
AC Power Frequency 50 / 60 Hz
Reactive Power Range Any
Protective Devices
DC Input Fuse and motorized load disconnector
AC Input Circuit breaker
Overvoltage Protections DC Type 1 + 2 SPD
Components PV Station
Inverter 2 x PV 4100 UEP 2 x PV 4300 UEP 2 x PV 4500 UEP 2 x PV 4700 UEP
Transformer* Dyn KNAN/ONAN
Switchgear* 0L1V / 1L1V / 2L1V up to 36 kV
Custom Auxiliary Transformer Optional
Others Auxilliary cabinet
Communications
Control Modbus TCP / IP (Profinet, CAN upon request)
Monitoring Modbus TCP / IP
Other Features
LVRT Yes
HVRT Yes
Working Ambient Temperature ** -20°C / +60°C (-4ºF / +140ºF). Option -40ºC (-40ºF)
Relative Humidity 100% (without condensation)
Max. Altitude (whithout derating) *** 2000 m (6561ft)
Dimensions W x H x D (IEC / UL version) (1) 11800 x 2600 x 2100 mm / 30 x 8.5 x 8.6 ft
Weight (IEC / UL version) (1) 26500 kg
Protection IP54
Cooling Liquid & forced air
Main Standards Optionals
IEC 62109 -40°C Low Temperature Kit
UL 1741-SA UPS for Supplying Trackers
UL 62109 Motorized MV Switchgear
NEC High Corrosion Protection Kit
Seismic Reinforcement

(1) UL variant only available for 1-inverter based configuration
* UL version: Padmounted Dyn (without external switchgear)
** With derating from 25ºC / 77ºF
*** Up to 4000 m (13123 ft) with derating, as optional

Do you need more information?

Our team is at your disposal

Contact us