NEW!
Gamesa Electric
PV 3750

Maximum energy for utility-scale projects

Outdoor Solution
Efficiency
Gamesa Electric PV 3750

Driving
LCoE down

better

Better LCoE

Compact design which allows 2-inverter solution of up to 7.500 kVA in a standard 40ft skid, achieving  overall cost reduction by using less PV station units per project.

Design with best-in-class components that guarentees less probability of failure and therefore less operation cost (materials and workforce).

Market leading inverter efficiency of 99%.

reliability

Reliability

Smart liquid/air cooling system that allows critical components to work at temperature level far below the limit, guaranteeing product life span.

Tier I supliers for critical components (power semiconductors, capacitors, inductances and control cards) with best-in-class MTBF values.

“Easy to support” concept, with heavy components in removable trays, reducing maintenance and repair time (MTTR).

world

Grid compliance

An extensive list of grid-codes compliance, including the most demanding ones, such as Germany, Mexico, Jordan, South Africa and more.

Full operating range reactive power supply for both day and night operation through the so-called Statcom mode.

Non-characteristic harmonics cancellation over distorted and unbalanced grids (weak grids).

.

Factory-tested
  • Two full power test benches available with 3.5 MW and 5 MW capacity
  • Upgrade to 6 MW by end of 2019
  • Each test bench has:
    • High speed drives made in house (motors and drives)
    • Virtual grid to perform 50/60Hz, PQV curve characterization, HVRT/LVRT and weak grid tests
    • Water-cooled systems and close-loop transformers to minimize grid losses consumption
  • Outdoor design IP54 & NEMA 3R C4H
  • Up to 60ºC operating
  • Water + Air Cooling System
  • Better for dusty environment
  • Selective Cooling
  • Continuous Temp. monitoring
  • H <= 2000 m
  • Tier I suppliers for main components
  • Field-Proven Components: CCU
  • Control Unit (CCU) MTBF: 40 years (over a 2.000 units population*)

    * Currently there are more than 6500 units in operation (G5x, G10x and PV Inverters). Study has been carried out on 2.000 units and more than 40 million operating hours.

  • Easy Access to main components
  • Easy to Maintain
  • MTTR
  • Reactive power generation with constant power factor in the inverter
  • Variable reactive power according external control/commands:
    • To maintain PCC voltage
    • To maintain PCC power factor
    • Night reactive generation
    • To compensate power factor of an installation connected to common PCC
  • Gamesa Electric Inverter is able to generate reactive power at night up to nominal power with an active power consumption < 2% of the generated reactive power
Gamesa Electric PV7500

Introducing the best performance

even under harsh enviroments

NEW!
Gamesa Electric
PV 7500

Larger MV solution
for LCoE reduction

Less units needed per project, which results in lower equipment cost

Reduced costs of transportation, offloading and site preparation

Solution delivered pre-assembled, configured and tested, reducing on-site labour cost

Gamesa Electric PV 3750
Input (DC)
DC Voltage Range 915-1500 V
DC Voltage Range, MPPT 915-1300 V
Maximum DC Voltage 1500 V
Max. DC Current @25°C 2 x 2070 A
Max. DC Current @50°C 2 x 1990 A
DC/AC Ratio 1.60
Number of DC Ports Up to 24 fuse +/- monitored
Up to 36 fuse + monitored
Output (AC)
Number of Phases Three-phase
Nominal AC Power @25°C 3750 kVA
Nominal AC Power @50°C 3600 kVA
Nominal AC voltage 660 Vrms
AC Power Frequency 50/60 Hz
THD of AC Current < 3% @Sn
Power Factor Range -1 to 1
Performance
Max. Efficiency* 99.0%
Euro-Efficiency* 98.8%
Californian-Efficiency* 98.6%
Stand-by Power Consumption* < 200 W
Energy Production from 0.5% Pn approx
General Data
Temperature Range - Operation** -20°C / +60°C
Maximum Altitude*** 2000 m (without derating)
Cooling System Liquid + forced air cooling
Protection Class IP54, NEMA 3R
Dimensions (W/H/D) 3508 x 2250 x 1022 mm
Power Density @25°C 465 kVA/m3
Power Density @50°C 446 kVA/m3
Weight 3200 kg
Features
Communications Modbus TCP-IP
Overvoltage Protection AC Type I + II SPD
Overvoltage Protection DC Type I + II SPD
DC Side Disconnection Motorized DC load switch and fuse
AC Side Disconnection Motorized AC circuit breaker
Main Standards
IEC 62109
IEC 61000-6-2
IEC 61000-6-4
IEC 62116
IEC 61683
IEC 60529
IEC 61727