Gamesa Electric

  1. Home
  2. Products
  3. Photovoltaic
  4. Gamesa E-1.4 MVA & Gamesa E-1.3 MVA/1.1 MW
 

Gamesa E-1.4 MVA & Gamesa E-1.3 MVA / 1.1MW

Description

  • Inversores Gamesa E-1MW/ 1,25MWGamesa Electric PV Inverter with DC Input Voltage Range up to 1.000 VDC.
  • Hybrid water and air cooling technology enhances operational temperature range: up to 50ºC (122ºF) without de-rating and up to 65ºC (149ºF) before shut-down.
  • High power density, complete solution in a 20-ft container; two units in a 40-ft container reaching up to 2.8MVA (including  inverter/s + step-up transformer + switchgear).
  • Reduction of the cost/kW of the complete PV station.
  • Highly competitive CoE, based on technological innovation and continual improvement.
  • Easy to manufacture, easy to maintain: modular design eases access to components and facilitates maintenance.
  • Maximum reliability and robustness, underpinned by Gamesa’s experience in the demanding wind power sector. Exceptional performance in the harshest, most demanding environments.
  • Two independent Max Power Point Trackers (MPPT) which optimize the energy harvesting and increase overall efficiency.
  • Grid code compliance oriented. Voltage and power stabilizer: advanced controls for both active and reactive power: fast ramp-up (active & reactive), power factor stabilization, voltage stabilization, optional full reactive current injection at night (stat-com mode), active power regulation.
  • Tropicalized control cards allow the inverter to work in very high humidity and dust environments.
  • Built-in web server for remote monitoring and control.

 

Technical file

 
DC INPUT VALUES

GAMESA E-1,4MVA

GAMESA
E-1,3MVA/1,1MW
Recommended PV-Power 1.400-1.800 kWp 1.300 kWp
Maximum DC current @ 50ºC
2.100 A 1.800 A
DC Voltage range
610 – 1.000 V 570 – 1.000 V
DC MPPT Voltage range
610 - 910 V 570 - 910 V
Nº of DC ports
12
12
Section max. cable per phase
2 x 300 mm2 2 x 300 mm2
Energy production from
0,5% Pn aprox. 0,5% Pn aprox.
     
AC OUTPUT VALUES    
No. of phases 3 3
Apparent power 1.400 kVA 1.300 kVA
AC Active Power @ PF 1 & 50ºC
1.370 kW 1.100 kW
Nominal AC voltage 400 Vrms 360 Vrms
Voltage allowance range -15 % / +10% -15 % / +10%
Output frequency 47.5...53/57...63 Hz 47.5...53/57...63 Hz
Power factor See P-Q curve 0.76 IND - 0.76 CAP
THD of AC current
<3% @ Pn <3% @ Pn
Max. AC current per phase @ 50ºC 2.020 Arms 1.760 Arms
Max. AC current per phase @ 25ºC 2.165 Arms 2.165 Arms
Section max. cable per phase
6 x 300 mm2 4 x 300 mm2
     
PERFORMANCE    
MPPT
2 2
LVRT/HVRT
98.4% 98.4%
Permissible ambient temperature Yes Yes
Relative humidity
-20ºC / +50ºC (65ºC*) -20ºC / +50ºC (65ºC*)
Max. Altitude
95% (without condensation)
95% (without condensation)
Dimensions (width x height x depth)
3.000 m
3.000 m
Weight
2.450 x 1.840 x 1.035 mm
2.450 x 1.840 x 1.035 mm
Cooling Dimensions (width x height x depth)
1.700Kg
1.700Kg
Protection degree
1.000 x 1.200 x 1.000 mm
1.000 x 1.200 x 1.000 mm
Cooling
IP-20 indoor
IP-20 indoor
  Liquid + Forced Air Liquid + Forced Air
MAIN STANDARDS    
CEM: EN 61000-6-2, EN 61000-6-4
   
EN 50178
   
CE marking
   
     
For more information, please, contact Gamesa Electric
   
 (*) With derating from +50ºC to +60ºC